A sound rack server configuration starts with the workload, not the hardware. Work out how much power and cooling each rack can really receive, pick a rack that fits the servers you plan to buy, put the heaviest gear at the bottom, keep airflow and service paths clear, and commission everything in stages before production load arrives. This guide walks through that sequence for HPC and AI racks, where density makes every shortcut more expensive.
TL;DR
- Size the rack around power and cooling limits first. Floor space is rarely the constraint in HPC and AI deployments.
- Check the rack itself: EIA-310 19-inch mounting, enough depth and height, and a load rating that covers fully populated GPU servers.
- Install from the bottom up with the heaviest device lowest, fill gaps with filler panels, and never leave more than one server extended.
- Route cables out of airflow and service paths, label both ends, and keep a record of every run.
- Commission in stages with a representative high-load job before the rack carries production work.
Table of Contents
- Start with the workload, not the rack
- Choose a rack that fits the servers
- Arrange equipment inside the rack
- Mount servers and rails safely
- Power distribution
- Cooling and airflow
- Cabling that does not fight airflow
- Commission before you load production
- Our perspective
- Plan your rack build with Dormedia
- FAQ
- Sources
Start with the workload, not the rack
A rack is a container for power, cooling and network connections as much as for servers. The practical limit on how many servers you can install is usually one of these: a branch circuit, one side of an A/B power feed, a rack PDU connector, an upstream UPS module, local airflow, a coolant loop or floor loading. An Edilec guide to rack power density recommends beginning with the workload: node count, CPU and accelerator power modes, steady demand, synchronized compute peaks, boot and firmware-update behavior, and planned growth.
That approach beats reading nameplate wattage off a spec sheet. GPUs that ramp together create power steps that a breaker has to absorb, so the headroom you thought you had can disappear the moment several nodes start the same job.
A useful planning table has one row per server type and these columns:
| Item | What to record |
|---|---|
| Node count per rack | Target now and at full build-out |
| Power per node | Steady draw, peak draw, boot behavior |
| Power feeds | Voltage, phases, A/B redundancy |
| Heat output | Air, liquid or hybrid cooling path |
| Network | Ports per node, cable type, maximum run length |
| Weight | Loaded server weight and total rack weight |
Fill this out before you order a rack. It also tells you whether the room you have can host what you want, a question we cover in our guide to data center site selection for HPC and AI.
Density sets the layout
NVIDIA's DGX SuperPOD data center design guide says DGX H100 systems are optimally deployed four per rack, with density adjustable to the power and cooling available. It also warns that rack density affects floor layout and network cable lengths, so facilities and network teams need to plan together. In the same document, InfiniBand cable travel must not exceed 50 m.
Supermicro's blueprint for large-scale GenAI infrastructure frames the rack as an extra tier of organization beyond the compute node. You optimize it for goals such as shorter cables, easier deployment and service, better thermal performance and higher space utilization. Our own guide to high-speed interconnects for HPC and AI explains how topology choices feed back into rack placement.
Choose a rack that fits the servers
General-purpose racks often fail with AI hardware. The servers are deeper and heavier, and they need more room for power and cabling.
For reference deployments, NVIDIA requires racks that conform to EIA-310 for enclosed 19-inch mounting, at least 24 in × 48 in (600 mm × 1,200 mm) and at least 48U tall. It recommends 32 in × 48 in (800 mm × 1,200 mm) racks for cable management, rPDU placement, airflow management and rear service clearance.
Schneider Electric's white paper on AI data center design gives similar guidance for AI clusters:
- Racks at least 750 mm (29.5 in) wide
- At least 48U high and 1,200 mm (47.2 in) deep
- Mounting depth of 1,000 mm (40 in)
- Static weight capacity above 1,800 kg (3,968 lb)
- Dynamic weight capacity above 1,200 kg (2,646 lb), validated by an independent third party
The static figure covers a rack standing still. The dynamic figure matters while the rack is rolled into position, so check both against the loaded weight in your planning table, plus the floor rating on the route to the final position.
Fit-check before delivery
The 19-inch mounting interface (IEC 60297) does not define a cabinet's outer width or depth. Two racks that both claim 19-inch compatibility can differ in rail travel, door setback and cable channel space. NVIDIA's guide asks you to document these on project drawings and to fit-check rail assemblies at the top, middle and bottom positions. Do this with a sample rail kit or the vendor's drawings before a full order lands on the dock.
Also confirm the practical details: side walls where the design needs them, no open chimneys that let hot air recirculate, and room behind the rack for a technician and a cart.
Arrange equipment inside the rack
Layout order is simple, and the reasons are mechanical.
- Plan from the bottom up. Lenovo's rack installation instructions say to start at the bottom and install the heaviest device lowest.
- Put UPS units and battery packs at the bottom. A RackLedge layout guide notes these are the heaviest items and that low placement keeps the center of gravity near the floor. It also suggests leaving the U directly above a UPS empty for battery expansion or airflow.
- Group by function. Compute, storage, switches and power distribution each get a defined zone so that service on one does not disturb another.
- Reserve space. Leave room for growth now. Retrofitting a populated rack is slower and riskier than installing into planned gaps.
- Cover every gap. Lenovo's guidance is to not leave open space above or below an installed server, and to use a filler panel so air does not bypass the equipment.
Rack elevations should show every element: servers, blanking panels, power distribution, switches, patch panels, manifolds, coolant distribution units, cable managers and reserved space. Linuxclusters.com adds a useful test: a failed piece of hardware should be removable without disconnecting unrelated equipment. If your elevation fails that test on paper, it will fail on the floor.
Top-of-rack switches and heavy GPU nodes
Where you place the switch depends on your topology. Top-of-rack placement shortens cables for traditional leaf designs, while GPU clusters with rail-optimized fabrics may use a different arrangement. Decide this alongside the interconnect design, not after the rack is racked.
Mount servers and rails safely
Racking a server is a two-person job once the chassis is large. Lenovo's instructions require two or more people to install 2U, 4U or larger devices. Dense GPU servers are well past that threshold, and many sites use a server lift.
The general sequence for rail-mounted servers:
- Attach the rail members to the chassis and to the rack, matching the rack's hole type (square or round) and depth.
- Confirm the rails are locked in position at both the front and the rear.
- Slide the server in and secure it with the screws the vendor specifies. Lenovo's rail instructions use M5 screws.
- Connect power and network, then test that the server slides in and out without binding on cables.
Two safety rules apply on every build. Do not extend more than one device out of the rack at a time, because a pulled-out server shifts the center of gravity. And do not block air vents: Lenovo notes that about 15 cm (6 in) of air space typically provides proper airflow. If your rack has stabilizing feet or anchoring, deploy them before you start loading.
Power distribution
High-density racks need higher-voltage distribution. AMD's data center design guide points to 380 to 415 V AC or 48 V DC inside racks, along with redundant power distribution, UPS and backup power.
NVIDIA's reference design for DGX H100 is a good example of what a specification looks like. Its preferred power is 415 VAC, 32 A, three phase, N+1, with at least three power sources to each rack (rPDUs fed by separate upstream paths), each sized for 50% of the total peak load. Four of the six internal power supplies must be energized for a DGX H100 system to operate, which is why feed redundancy has to be designed for specific failure cases rather than assumed.
Two habits prevent most power surprises:
- Model peak, not average. Synchronized GPU ramps are a real design case.
- Label every circuit and rPDU outlet, then check the labels against the one-line diagram and panel schedule before energizing.
Electrical installation rules and protective-device coordination depend on your jurisdiction and the actual distribution design. In the United States, your facilities engineer or licensed electrician should approve the capacity calculation and supervise any electrical testing. Elsewhere, the equivalent local authority applies.
Cooling and airflow
Cooling follows density. The U.S. National Renewable Energy Laboratory lists recommended equipment intake temperatures of 65 to 80°F, with an allowable range of 59 to 90°F for Class A1 equipment. Those are the numbers to design against for air-cooled gear.
As racks climb, air stops being enough. Vertiv's liquid cooling white paper reports rack requirements above 20 kW in a growing number of facilities and many organizations deploying 50 kW or more, where air cooling becomes untenable economically. AMD's design guide goes further: at 300 to 400 kW per rack, traditional air cooling is not optimal or feasible, and direct liquid or immersion cooling is needed.
Most real deployments sit between the extremes. A SubZero Engineering white paper on hybrid cooling explains that direct-to-chip liquid cooling targets CPUs and GPUs while air still has to remove roughly 25% or more of the residual heat in HPC racks. Plan airflow even in a liquid-cooled rack.
| Rack power range | Typical cooling approach |
|---|---|
| Up to about 20 kW | Air cooling with containment and blanking panels |
| About 20 to 50 kW and above | Air with rear-door or direct-to-chip liquid assist |
| Very high density (hundreds of kW) | Direct liquid or immersion cooling |
Treat the table as an orientation guide drawn from the sources above. Your actual thresholds depend on the room, the equipment vendor's requirements and the cooling plant.
Co-design power and cooling from the start. AMD's guide notes that liquid cooling loops often share pathways with busways, so a late change to one forces a redesign of the other.

Cabling that does not fight airflow
Cable management is part of cooling performance. The U.S. Department of Energy's best practices guide for energy-efficient data centers says a cable strategy should minimize obstructions along the whole cooling airflow path, including rack intake and discharge, and recommends removing abandoned cables to improve cooling delivery.
Practical rules:
- Use vertical cable managers that keep runs out of the air path, and leave disciplined slack rather than long loops.
- Respect bend radii and pull limits, and support the weight of cable bundles so connectors do not carry it.
- Keep cables out of service paths so a technician can pull a server without unplugging its neighbors.
- Label both ends of every cable, and keep a record of type, length, source and destination. The physical record is how you verify and repair the logical topology later.
- Check rack depth. A rack that is too shallow can break airflow seals and make cable management close to impossible, as Obelinf's rack layout guide points out.
For fabric cables, remember the length limits that come with your interconnect. The 50 m InfiniBand limit in NVIDIA's design is a hard boundary on how far apart racks in a pod can sit.
Commission before you load production
The last stage is the one teams rush. Before the rack carries real work, verify the physical design against the documents.
Check the paperwork against the room
Compare rack elevations with one-line electrical diagrams, panel schedules, breaker and outlet labels, cable maps, coolant diagrams, valve positions, alarm routes, equipment ratings and the final bill of materials. Then walk the physical routes: rack anchoring and leveling, clearances, blanking panels, cable and hose supports, bend radii, and leak detection and fire systems where installed.
Stage the power-on
An Anvilfield commissioning field guide says the facility must be commissioned and stable before cluster commissioning starts. It also says GPUs must not be powered into load before cooling loops are proven, and that power-on should happen in staged blocks to control inrush current and catch faults at the smallest possible scope.
Run a representative load
The Edilec guide recommends commissioning with the intended equipment population and a representative high-load job. During that run, verify:
- Phase currents and rack PDU alarms
- Power-supply redundancy
- Inlet and return temperatures
- Coolant values where liquid cooling is in use
- Fan behavior, controls, telemetry and labeling
Exercise permitted failure scenarios under change control, such as losing one power feed. Qualified facilities personnel should define and supervise electrical tests.
If the rack ships from another country, delivery planning belongs in the same schedule. Our guides to data center logistics and data center migration planning cover moves, delivery windows and lifecycle handling.
Our perspective
Most rack problems we see were decided long before anyone picked up a screwdriver. A team orders servers first, then discovers that the room cannot deliver the power, that the rack is too shallow for the cabling, or that the pod's cable lengths do not work. Fixing that on site costs far more than a day of planning.
Our approach is to treat the rack configuration as one project across sourcing, design, delivery and deployment. We have worked in HPC and AI infrastructure since 2017, and in technology sourcing since 2011. We start from your workload and the power and cooling you can actually get, then specify servers, components, racks and networking to match, and build the logistics and tariff handling around that plan.
The benefit of a single accountable team is fewer handoffs. The person who chooses the rack depth also knows what cable you ordered and when the pallets reach the dock. For customized configurations, global deployments and staged scale-up, that continuity is what keeps a build on schedule.
Dormedia
Plan your rack build with Dormedia
If you are specifying racks for an HPC or AI project, we can help with the whole path: server and component sourcing, customized configurations, data center solutions, global shipping, tax and tariff handling, project management and ongoing support. Tell us the workload and the target site, and we will help you turn it into a build plan.

Start at Dormedia to discuss a project, or browse available hardware inventory to see what can be sourced.
FAQ
How many servers should go in one rack?
It depends on the power and cooling delivered to that rack, not on the number of U spaces. NVIDIA, for example, describes four DGX H100 systems per rack as the optimal deployment, adjustable to available power and cooling. Build your planning table first, then fill the rack up to the lowest limit you find.
Where does the heaviest equipment go?
At the bottom. Lenovo's instructions say to plan installation from the bottom of the rack and put the heaviest device lowest, and UPS units and battery packs are the heaviest items in many racks. Low placement keeps the center of gravity near the floor and makes the rack more stable during service.
What rack size do I need for AI servers?
For DGX SuperPOD-style deployments, NVIDIA requires EIA-310 racks of at least 24 in × 48 in and 48U, and recommends 32 in × 48 in. Schneider Electric's AI guidance adds at least 1,200 mm depth and static capacity above 1,800 kg. Confirm the exact numbers against your server vendor's documentation.
Do I need blanking panels?
Yes. Lenovo's guidance is to cover open space above or below an installed server with a filler panel to maintain proper air circulation. Panels stop hot exhaust air from looping back to the server intakes.
What should I test before going live?
Run the intended equipment with a representative high-load job and check phase currents, PDU alarms, power redundancy, temperatures, coolant values, fans and telemetry. Stage the power-on in blocks, and have qualified facilities staff supervise the electrical tests.
Sources
- NVIDIA DGX SuperPOD Data Center Design
- Supermicro: A Blueprint for LLM and GenAI Infrastructure at Scale
- Schneider Electric: The AI Disruption, Challenges and Guidance for Data Center Design
- Lenovo: Rack Installation Instructions
- RackLedge: Rack Layout and Weight Distribution
- Edilec: Rack Power Density Planning
- AMD Instinct: Data Center Design Guide
- NREL: Trends in Data Center Design
- Vertiv: Understanding Data Center Liquid Cooling Options
- SubZero Engineering: Cooling the Future
- U.S. DOE: Best Practices Guide for Energy-Efficient Data Center Design
- Obelinf: Data Center Rack Layout
- Anvilfield: AI GPU Cluster Commissioning and Burn-in Field Guide